Voltage Drop Calculator

Estimate voltage drop and resistive losses in DC, single-phase AC, and balanced three-phase circuits.

This calculation models voltage loss. Check conductor ampacity, overcurrent protection, terminal ratings, and locally adopted electrical requirements before selecting an installed circuit.

Result
—

How to calculate

Use one-way length, wire resistance, and the phase-dependent factor. For AC include lagging power factor and reactance when known.

Worked example

Use Circuit DC · Conductor size 12 · Conductor metal Copper · Voltage (V) 120 · Current (A) 15 · One-way conductor length (ft) 100 · Conductor temperature (°C) 20 · Lagging power factor (0 to 1) 1 · AC reactance per 1,000 ft (Ω) 0. The result is ≈ 4.764657772016 V.

Input and result notes

Use line-to-line voltage for three-phase. This is a short-line approximation. Very large predicted drops indicate that the assumed operating point needs verification.

NIST copper wire tables