Three Phase Calculator

Calculate real, apparent and reactive power, line current, or voltage for a balanced three-phase wye or delta system.

Result
—

How to calculate

Multiply line voltage by line current and √3 for apparent power. Multiply apparent power by the power factor for real power. Use the magnitude of sin φ for reactive power, with a negative sign for leading loads.

Worked example

Use Calculate Power from voltage and current · Balanced load connection Wye (star) · Line-to-line RMS voltage (V) 400 · RMS line current (A) 10 · Power factor as a decimal from 0 to 1 0.8 · Reactive power direction Lagging (inductive). The result is ≈ 5.54256258422 kW.

Input and result notes

Use balanced sinusoidal steady-state loads and RMS values. Wye branch voltage is line voltage divided by √3. Delta branch current is line current divided by √3.