Boiler Size Calculator

Size a steam boiler from connected radiator EDR, or estimate a hot water boiler’s output from design heating load.

Result
—

How to calculate

For a steam system, multiply square feet of connected steam radiation by 240 BTU/h and compare to the boiler’s net rating. For hot water, use the design heat loss and any allowance you enter.

Worked example

Use Boiler sizing method Steam from connected radiator EDR · Connected radiator EDR (ft²) for steam 250 · Design heating load (BTU/h) 48000 · Extra allowance for output (%) 0. The result is ≈ 60000 BTU/h.

Input and result notes

For steam, use rated radiator EDR and compare to the published Net AHRI steam rating. That rating already includes a pickup allowance. The other inputs are for hot water sizing. Envelope mode uses steady-state loss and standard air density. Subtract windows and doors from wall areas before entering them as separate surfaces. Compare rated output at your design conditions and use a project-specific load calculation for equipment selection.

Weil-McLain steam boiler replacement guide

US DOE guidance on HVAC sizing

Related calculators